Danfoss EMP 2 Pressure Transmitter in Box Design
- High repeatability
- Interchangeable contact system
- Two cable entries
- IP66
- CE marked in accordance to EN 60947-4-5 and EN 60730-2-1/-9
- Ship approved (contact for full details)
- Other versions available with:
Duct sensor
Other capillary tube lengths
Adjustable neutral zone
Alternative regulation ranges
Technical Data |
Ambient temperature : |
-50oC to 70oC |
Enclosure : |
IP66; Manual reset version : IP54 |
Electrical connection : |
Two Pg13.5 (cable diameters 6 to 14mm) |
Contact system : |
SPDT, interchangeable to other types |
Contact load : |
AC-1 Ohmic : 10A, 440V |
|
AC-3 (motor) : 4A, 400V |
AC-14/15 (coil / transformer): 3A, 400V |
DC-13/14: 12W, 230V |
Code No |
Weight Kg |
Operating pressure relative (gauge) pe(bar) |
Connection |
Test pressure Pe (Bar) |
Min. bursting pressure Pe (bar) |
084G2106 |
1.06 |
0 to 4 |
G1/2" A male & G 1/4" A female |
8 |
200 |
084G2107 |
1.06 |
0 to 6 |
G 1/2" A male & G 1/4" A female |
18 |
400 |
084G2109 |
1.12 |
0 to 10 |
G 1/2" A male & G 1/4" female |
20 |
400 |
|
|